No-load performance test of diesel generator set: the main assessment data include engine water temperature, oil pressure, battery voltage, operating stability, and generator electrical parameter (frequency, voltage) stability;
Diesel generator steady-state no-load performance test: the main assessment data are generator frequency and voltage fluctuation range, generator frequency and voltage drop rate and rise rate, generator frequency and voltage setting test;
Load loading process (0%-25%-50%-75%-100%-110%-100%-75%-50%-25%-0%), the load test time is generally 1 hour, 100% load 20 minutes, the assessment data includes the voltage and frequency fluctuations and setting data of the generator when the generator is loaded at each stage;
Generator sudden load and sudden load performance test: perform sudden load and sudden discharge test according to 50% of the common power of the unit. Assessment data: transient deviation and transient recovery time of generator voltage and frequency when sudden load is applied; When the load is unloaded, the transient deviation and transient recovery time of generator voltage and frequency;
Other mechanical performance tests of the diesel generator set: the main assessment data are noise test, vibration test, laser ranging to check the overall dimensions of the generator set, insulation test of special generators;
The protection performance test of the diesel generator set: the main assessment data are AMF mains power failure automatic start-stop control, float charging and engine charging functions, emergency stop function, fuel oil quantity display, engine water temperature and oil pressure and actual data check and correction, and other protections Shutdown function (high water temperature, low oil pressure, etc.), generator voltage and frequency protection functions.
Customer special requirements performance test: automatic oil replenishment system function, integrated ATS function, new instrument and indicator function,leakage protection function, etc.